Please Pay Inside E01 (Poll Error)
Fix Poll Errors and "Please Pay Inside" on DCR (E01, See Cashier, "Currently only indoor payment is allowed")
Use this guide when DCRs show “Poll Errors” and are not responding.
Error: "Currently only indoor payment is allowed" / "Please Pay Inside"
If you see this message at the pump, start here.
It’s a DCR communication symptom. It’s in the same bucket as:
“Please Pay Inside”
“Please Pay Inside E01”
“See Cashier”
“Pay Inside loading”
Blank DCR screen
“Currently only indoor payment is allowed”
Search terms: Please Pay Inside, Pay Inside, Pay Inside E01, See Cashier, Currently only indoor payment is allowed, Poll Error, Poll errors, DCR offline, DCR not located.
“Please Pay Inside” on the pump/DCR is not the same thing as POS “PayIn/Payout”.
This prompt usually means the dispenser card reader (DCR) is not communicating with the Site Controller (Commander).
Start here if the pump/DCR shows any of these:
“Currently only indoor payment is allowed”
“Please Pay Inside” / “Please Pay Inside E01”
“See Cashier”
“Pay Inside loading”
Blank screen
Or if the POS shows “Poll error” / “Poll errors”.
Common symptoms at DCRs
Poll Error
Please Pay Inside E01
See Cashier
Please Pay Inside
Pay Inside loading
Blank screen
Currently only indoor payment is allowed
These usually mean the DCRs and the Site Controller (Commander) are not communicating.
Wayne DCRs stuck on "Loading started"
Confirm the site is using Wayne DCRs.
Confirm whether your Wayne DCRs have a contactless reader.
If they do not have contactless, please contact the Helpdesk for assistance.
If they do have contactless, continue with standard DCR troubleshooting below.
Standard DCR troubleshooting
Start here if impacting only one or a few DCRs
Before Initializing the DCRs
Before Initializing the impacted DCRs which is Downloading to one or few DCRs, confirm:
The impacted pumps/fueling positions are Idle and
No Active transactions or customers on those impacted pumps.
This prevents Initialization errors and stuck fuel sales.
Before Downloading to All DCRs or Initializing All DCRs, confirm:
All pumps/fueling positions are Idle and
No Active transactions or customers at the pumps.
This prevents Initialization errors and stuck fuel sales.
Confirm whether DCRs respond
Have the site watch at least one affected DCR during the download.
Any screen change (Downloading/Loading, reboot, new prompt) usually means the DCR is receiving data from the Site Controller (Commander).
No change at all (same message, no flicker) usually means it’s not communicating with the Commander.
Forecourt status (OEMV / Ethernet)
Use this to confirm whether each DCR is communicating with the Site Controller (Commander).
In Config Client, go to:
Tools → Helpdesk Diagnostics → Forecourt
For each DCR, confirm:
Located → shows the DCR number.
Status → shows Online (communicating).
If the DCR is missing, not located, or shows Offline, the DCR is not communicating.

Start here if impacting all DCRs
Watch DCR screens during the Initialization
Any screen change usually means the Site Controller (Commander) is communicating with the DCRs.
No change at all usually means a communication issue.
If there’s no change, go to the DCRs over Ethernet (OEMV) or Serial guide.